Logged in as

Customer Service

Available jobs

Job opportunities at Elvaco

Elvaco is a growing company with talented, down-to-earth people who want to deliver that little extra while at the same time having fun!

 

Apply now!

CMi1020w

CMi1020w

The CMi1020w is a wireless meter module, tailor-made for the E350 electricity meter of Landis+Gyr. The device transmits power consumption data via a wireless M-Bus. With greater flexibility in mind, it is available with either a standardised or customised configuration. 

The CMi1020w is ideal for projects that do not require wiring. Its performance and easy use make the CMi1020w a reliable solution for smart metering. It ensures successful data transmission and optimises power management.

CMi1020w - Integrated MCM for Landis+Gyr E350

CMi1020w is an integrated meter connectivity module which is mounted in a Landis+Gyr E350 electricity meter to collect meter data and deliver it to a receiving system by Wireless M-Bus. The product can be ordered with a default or customized configuration. This makes CMi1020w a perfect option when a high degree of flexibility and an attractive price point is required and wiring is not an option, for example in sub-metering projects.
  • Total: 2
  • Total: 2

Mechanics

Casing material:
Polycarbonate
Dimensions (w x h x d):
166 x 92 x 35 mm
Protection class:
IP20
Weight:
125 g
Mounting:
In Landis+Gyr E350

Electrical connections

Supply voltage:
From L+G E350
Rate inputs:
Screw terminal. Cable 0.25-1.5 mm², 0.5 Nm tightening torque

Electrical characteristics

Nominal voltage:
220-240 VAC (+/-10%)
Frequency:
50/60 Hz
Power consumption (max):
<0.5 W
Installation category:
CAT 4
Rate input low voltage:
<10 VAC
Rate input high voltage:
>24 VAC
Rate input max voltage:
230 VAC
Rate input minimum detection time:
1 s

Environmental specifications

Operating temperature:
-40 °C to 70 °C
Operating humidity:
5 % to 90 %, non-condensing
Operating altitude:
0-2000 m
Pollution degree:
Degree 2
Usage environment:
Indoors
Storage temperature:
-40 °C to +70 °C

Temperature sensor, margin of error

Humidity sensor, margin of error

User interface

Green LED:
Power
Red LED:
Error

M-Bus

Interfaces:
M-Bus slave
M-Bus standard:
EN 13757-4. Communication by T1 (default) or C1

Wireless M-Bus

Integrated M-Bus Master

Wireless M-Bus Receiver

M-Bus slave interface

Frequency, Wireless M-Bus:
868.95 MHz
Addressing modes:
Electricity meter's secondary address
M-Bus information:
Default or custom configuration
Transmit power:
25 mW
Transmit interval:
16 to 510 seconds (default: 16 seconds)
Encryption:
Unencrypted (default) or encrypted

General

Data storage (examples)

Mobile Network

Fixed Network (Ethernet)

Integration

Meter implementation:
Landis+Gyr E350
Number of connected meters:
1

Approvals

EMC:
EN 301489-1, EN 301489-3
Safety:
EN 61010-1, CAT 4

Connections and Interfaces

Transmissions